Key features AGT Series features include True RMS Output – remains accurate on distorted waveforms like VFD or SCR outputs; Single Range – eliminates field range selection errors and zero and span pots; and Isolation – magnetically isolates output from the input for safety and eliminates insertion loss.
AGT Series specifications include:
- Output Signal: 4-20 mA, Loop-powered, True RMS
- Output Limit: 23 mA
- Accuracy: 1,0% FS from 10% to 100% of range
- Frequency Range: 40-400 Hz
- Power Supply: 24 VDC Nominal, 12-24 VDC
- Response Time: 600 ms (to 90% step change)
- Standards: UL, CUL 508 Listed